POWER BACK UP IN HOME -INVERTER & BATTERY SIZE CALCULATION

 

We usually use inverter in residential as well as in commercial building. We have to procure proper rating capacity of Inverter and battery for installation. To calculate proper size inverter, we follow following steps.

  • Calculation of Rating of Inverter:

First, we estimate the total power of appliances connected in the building.

Suppose, there are following appliances with given ratings

Sl No.

Name of the Appliance Power Rating (W) No of Appliances Total Power Rating(W)
1 Ceiling Fans 75 4 300
2 LED Bulb 10 6 60
3 TV 120 1 120
4 Computer 200 1 200
Total Power Connected

680

 

The power factor of individual domestic appliances varies from 0.6 to 0.8.

Average power factor =0.7

Total VA required=680/0.7=971.428

Nearest standard rating of the inverter should be 1000VA

  • Calculation of battery size:

Suppose we have to run the inverter at least for 4 hours during  distribution power failure.

Battery  Capacity=Total wattage/Battery Voltage X efficiency

=680×4/12Vx0.85=192.66 Ah

Nearest Standard Capacity of 12V Battery=200Ah

POWER BACK UP IN HOME -INVERTER & BATTERY SIZE CALCULATION